 |
Main features |  |
|
Power supply of the test bench: three-phase network (380 V, 50 Hz). Voltage deviation should be within the range of -10%... +10%.
Rated current while testing supply voltage not more than 1.7 A for each phase.
Test bench's rated current in the current transformer probe mode in the 380 V circuit - not more than 3 A.
Range of test bench output voltage change: 0…450 V.
Range of output current changes in the current transformer probe mode:
0...100 À;
0...400 À.
Note: test bench operation time under maximum probe current must not exceed 5 minutes with the following cooling for 20 minutes.
Discrete values of insulation resistance :
500kÎì ± 5%;
30 kÎì ± 5%.
The test bench supports:
- supply of three-phase voltage (50 Hz) to the tested object within the range 0…450 V
- linear output voltage control through indicator facility
- Possibility for certified instruments to be connected for output voltage control
- output voltage disbalance within the range of ±300%
- supply the tested object with monophase AC (50 Hz) within the range:
0...100 À;
0...400 À.
- monophase AC control through indicator
- simulation of two discrete values of insulation resistance:
500 kÎì ± 5%;
30 kÎì ± 5%.
|